Schneider Electric Acti9 iSD Auxiliary Contact A9A26907
The Schneider Electric Acti9 A9A26907 is an iSD auxiliary contact. It is also called a fault contact. Its job is to tell you when the circuit breaker next to it has tripped because of a fault. It does not react when someone switches the breaker off by hand, so the signal always points to a real problem. The contact has one changeover output, which you can wire to an alarm, a panel light or a PLC input. It works from 100mA to 6A at 24 to 415V AC and 24 to 130V DC, so it suits most low voltage control circuits. The body is only 9mm wide and clips onto the left side of the breaker. A small mechanical indicator on the front shows its state. Screw terminals at the bottom make wiring simple and clean. This is a reliable choice for distribution boards where staff need a quick fault alert.
Features of Auxiliary Contact A9A26907
- Fault signal only: it reports a trip caused by a fault, not a manual switch-off
- 1 C/O contact: one changeover output that can work as normally open or normally closed
- Wide range: works on both AC and DC control circuits from 100mA to 6A
- Slim 9mm body that saves space on the DIN rail
- Mechanical indicator on the front for a quick visual check
Technical Specifications of Auxiliary Contact A9A26907
- Range: Acti9
- Device short name: iSD
- Product type: Fault contact
- Contacts: 1 C/O
- Rated insulation voltage (Ui): 500V
- Rated impulse withstand voltage (Uimp): 4kV
- Standards: EN/IEC 60947-5-1 and GB/T 14048.5
- Marks: CE and UKCA, with EAC, CCC and CMIM quality labels
Rated Current and Voltage of Auxiliary Contact A9A26907
- 24 to 240V AC: 0.1A to 6A
- 415V AC: 0.1A to 3A
- 24V DC: 0.1A to 6A, 48V DC: 0.1A to 2A
- 60V DC: 0.1A to 1.5A, 130V DC: 0.1A to 1A
Size and Mounting of Auxiliary Contact A9A26907
- Size: 86mm high, 9mm wide, 73mm deep
- Weight: 33g
- Mounting: clip-on on the left side of the circuit breaker, on a DIN rail
- Connection: screw terminals at the bottom, 1 cable of 1 to 4mm² (rigid) or 0.5 to 2.5mm² (flexible)
- The comb busbar can be used on the top side
Compatibility of Auxiliary Contact A9A26907
- Single terminal Acti9 iC60 and iC60 RCBO
- Acti9 iID, iDPN Vigi and iC40
- Acti9 iSW-NA, ARA and RCA
- Compatibility code: iSD
Installation Usage or Safety
- Switch off the power and check that the circuit is dead
- Clip the contact onto the left side of the breaker
- Connect the signal wires to the bottom terminals and tighten them well
- Switch the power on and test the signal at your alarm, light or PLC
- Electrical work should be done by a qualified electrician
Where to Use This
- Distribution boards in small commercial buildings
- Control panels that need a fault alarm
- Remote monitoring of breaker trips
- PLC and building system fault inputs
Package Includes
- 1 x Acti9 iSD auxiliary contact A9A26907
Why Buy From Sensato Trade
- You get the original Schneider Electric part. The part you receive is genuine and fully compatible.
- You get customer support that is ready to help if you are not sure about compatibility or have any other questions about the product.
- Fast and secure delivery is available, across Pakistan.
- Sensato Trade is a seller who truly understands industrial parts.
- We offer a refunds and returns policy if the product does not match your needs or if there is a compatibility issue.
Frequently Asked Questions
Q1: What does the iSD contact signal?
It signals that the device has tripped because of a fault.
Q2: Does it signal a manual switch off?
No. Use an iOF contact if you want to know whether the breaker is open or closed.
Q3: Can I use it on DC circuits?
Yes. It works from 24 to 130V DC, but the allowed current drops as the voltage goes up.